The I/O line SIMATIC ET 200SP HA can now be configured in STEP 7 from V5.6 onwards.
The I/O line SIMATIC ET 200SP HA can now be configured in STEP 7 from V5.6 onwards.
The provided Hardware Support Packages (HSP) enable you to configure the SIMATIC ET 200SP HA modules that are not yet included in the hardware catalog of your STEP 7 installation.
The procedure how to update the hardware catalog of your STEP 7 installation with this download is described in the following entry
How can you update the hardware catalog without direct internet access?
Download
The required HSP are included in the STEP 7 HSP collection. The download is provided via the following article
STEP 7 V5.x Hardware Support Packages (HSPs - as at 07/2019) for installing hardware updates in the Hardware Configuration
The following HSP are required for configuring the ET 200SP HA:
- HSP0272: IM 155-6 PN
- HSP0273: AI
- HSP0274: AQ
- HSP0275: DI
- HSP0276: DQ
- HSP0277: RQ
- HSP0278: Busadapter
- To operate ET 200SP HA in STEP 7, the latest firmware must be installed on the interface module.
The firmware can be obtained here Firmware update: ET 200SP HA Interface Module IM155-6 PN
Restricions
The full range of functions of the SIMATIC ET 200SP HA can only be realized in combination with a CPU 410 V8.2 or higher from STEP 7 V5.6.
When using the SIMATIC ET 200SP HA in STEP 7 together with S7-400 V6H, S7-400 V7 and CP443-1EX/GX30 V3.2, the following restrictions apply:
- no Configuration in Run
- no Sequence of Events
- no highly available Profinet structure R1 (redundant CPU with redundant interface module)
- I/O redundancy is possible with the SIMATIC S7-400 V6H, but no redundancy library is available.
- Overview of functions
1) No library support available
2) Used as PN controller
3) Project-specific release
ET 200SP HA hardwaresupport packages for STEP 7 are available in the following entry: 23183356
STEP 7 Project engineering with I/O redundancy
I/O redundancy is possible in STEP 7 with the SIMATIC S7-400 V6H. A library is not available. The following project planning regulations must be observed:
- Observe slot rules for I/O redundancy according to system manual ET 200SP HA (Entry ID109761547)
- In the case of input modules (DI; AI), the respective input data is read by both modules in redundancy mode. The QI bits must be taken into account when deciding on one of the two values.
- With digital outputs (DQ), the outputs are linked wired-or in redundancy mode; for a "0" at the output, both modules must output "0".
- In the case of analog output (AQ), only the setpoint value is specified, even in redundancy mode. The redundancy partners then automatically output half the target current.
- All diagnoses are identically available in redundancy mode, and redundancy-specific maintenance messages are also available.
Additional keywords
HSP, module catalog, HW-config, HW-update, hardware project engineering, projected module, update, upgrade, update
Additional information
SIMATIC ET 200SP HA Distributed I/O system