DCS/SIMATIC PCS7 PLC和组件HMI人机界面通信与网络组件过程控制系统过程仪表及分析仪器工业识别工业信息安全
DCS/SIMATIC PCS7
过程安全系统/安全仪表系统
SIMIT
SIMATIC PCS neo
更多
常问问题

Operation of the ET 200SP HA with STEP 7 V5.6

star star star star star
5.0 分
文档编号:109768649| 文档类型:常问问题| 发布时间:2023年12月04日
  • 0
  • 990
  • 33
The I/O line SIMATIC ET 200SP HA can now be configured in STEP 7 from V5.6 onwards.

The I/O line SIMATIC ET 200SP HA can now be configured in STEP 7 from V5.6 onwards.


The provided Hardware Support Packages (HSP) enable you to configure the SIMATIC ET 200SP HA modules that are not yet included in the hardware catalog of your STEP 7 installation.

The procedure how to update the hardware catalog of your STEP 7 installation with this download is described in the following entry
How can you update the hardware catalog without direct internet access?

Download
The required HSP are included in the STEP 7 HSP collection. The download is provided via the following article
STEP 7 V5.x Hardware Support Packages (HSPs - as at 07/2019) for installing hardware updates in the Hardware Configuration

The following HSP are required for configuring the ET 200SP HA:

  • HSP0272: IM 155-6 PN
  • HSP0273: AI
  • HSP0274: AQ
  • HSP0275: DI
  • HSP0276: DQ
  • HSP0277: RQ
  • HSP0278: Busadapter

  • To operate ET 200SP HA in STEP 7, the latest firmware must be installed on the interface module.
    The firmware can be obtained here Firmware update: ET 200SP HA Interface Module IM155-6 PN

Restricions

The full range of functions of the SIMATIC ET 200SP HA can only be realized in combination with a CPU 410 V8.2 or higher from STEP 7 V5.6.

When using the SIMATIC ET 200SP HA in STEP 7 together with S7-400 V6H, S7-400 V7 and CP443-1EX/GX30 V3.2, the following restrictions apply:


  • no Configuration in Run
  • no Sequence of Events
  • no highly available Profinet structure R1 (redundant CPU with redundant interface module)
  • I/O redundancy is possible with the SIMATIC S7-400 V6H, but no redundancy library is available.

  • Overview of functions

1) No library support available
2) Used as PN controller
3) Project-specific release

ET 200SP HA hardwaresupport packages for STEP 7 are available in the following entry: 23183356

STEP 7 Project engineering with I/O redundancy
I/O redundancy is possible in STEP 7 with the SIMATIC S7-400 V6H. A library is not available. The following project planning regulations must be observed:

  • Observe slot rules for I/O redundancy according to system manual ET 200SP HA (Entry ID109761547)
  • In the case of input modules (DI; AI), the respective input data is read by both modules in redundancy mode. The QI bits must be taken into account when deciding on one of the two values.
  • With digital outputs (DQ), the outputs are linked wired-or in redundancy mode; for a "0" at the output, both modules must output "0".
  • In the case of analog output (AQ), only the setpoint value is specified, even in redundancy mode. The redundancy partners then automatically output half the target current.
  • All diagnoses are identically available in redundancy mode, and redundancy-specific maintenance messages are also available.

Additional keywords

HSP, module catalog, HW-config, HW-update, hardware project engineering, projected module, update, upgrade, update


Additional information

SIMATIC ET 200SP HA Distributed I/O system
Delivery Release New 32-channel components for SIMATIC ET 200SP HA


您可以前往全球资源库查看此文档:

https://support.industry.siemens.com/cs/cn/zh/view/109768649/en

剩余80%未阅读,请登录后下载/查看文档

1847
  • 评论
  • 分享

    扫码分享

  • 收藏
  • 点赞
  • 纠错
 

隐私政策更新提示

欢迎您来到西门子数字化工业支持中心网站!我们使用cookies来确保您能最好地使用我们的网站,进行网站分析并根据您的兴趣定制内容。我们有时会与第三方共享cookie数据。继续浏览本网站,即表示您同意我们使用cookies。您亦可以参考西门子数据隐私政策以了解更多相关信息。

同意并继续浏览
提示
您即将前往“全球技术资源库”。
“全球技术资源库”的用户名与本地支持中心(下载中心、技术论坛、找答案、1847工业学习平台)的用户名不通用。如果需要在全球技术资源库下载文档,您需要重新登录或注册。
确定

0元领课点我

信息提示
很抱歉!您所访问的页面不存在,或网址发生了变化,请稍后再试。