- {{item.name}}
如何在 WinCC 运行情况下保存/拷贝项目?
- 0
- 1510
- 1
What are the options to create a backup of a WinCC V7/V8 SCADA system during operation?
B) SIDSI Backup & Restore Professional
Description
For the backup of a WinCC SCADA project with active runtime, only the two systems described below are tested and released.
Attention!
By using a non-released backup method of the WinCC project during running operation, there is a risk that the WinCC project is damaged or data is lost! Do not use any other solution than listed below in the running operation of WinCC in any case. Also creating snapshots as well as "Volume Shadow Copies" (VSS) are not allowed as long as WinCC is active.
"Veeam Backup & Replication" is only released for SCADA projects in the context of "SIDSI Backup & Restore Professional" (point B).
A) WinCC Tool "Copy Project"
The external WinCC tool "Copy Project" allows you to save the complete project including all databases during Runtime operation. This allows you to keep the project planning data consistent or to implement a clean change management for validated plants.
The backup of the WinCC project can be triggered manually or automatically via a call in a WinCC action. The data backup takes place in a directory specified by the user including the date stamp of the current day.
Note
This only functions correctly on a WinCC single-user station / multi-user system and with an active WinCC project.
The tool can be ordered via the following Article Numbers Copy WinCC Project:
9AE7141-2SS01-1AA0 for download (email)
9AE7141-2SS01-1AA1 on DVD (mail)
For more information, especially on licensing, supported operating systems and software requirements, see Delivery release Copy Project V7.0 (Entry ID 109822232).
B) SIDSI Backup & Restore Professional
Alongside, the preconfigured system "SIDSI Backup & Restore Professional" within the scope of "SIMATIC DCS / SCADA Infrastructure" (SIDSI) as of V2.1 offers among others the possibility to backup the entire system on which a WinCC project is running in Runtime. Released and tested is "SIDSI Backup & Restore Professional" exclusively using certain virtualization systems or SIMATIC IPCs.
Further information can be found here Data archiving and visualisation in automation plants under "Data archiving, visualization and backup".
Consultation
If you have any questions before placing an order, please contact the Siemens Technical Consulting office in your region.
PCS 7 systems
Which backup systems you can use during operation with PCS 7 is described in Entry 56897157.
Additional keywords
Live backup, disaster recovery solution
您可以前往全球资源库查看此文档:https://support.industry.siemens.com/cs/cn/zh/view/38493803 |
剩余80%未阅读,请登录后下载/查看文档
- 评论
-
分享
扫码分享
- 收藏 收藏
- 点赞 点赞
- 纠错 纠错
- 如果FB块被多次调用,如何监控单个块的执行情况?
- 如何在 WinCC Comfort 和 WinCC Advanced 中安全地拷贝或移动归档数据?
- 如何在不进行砝码标定的情况下更换称重模块
- 如何在没有 STEP 7 Basic 的情况下修改 S7-1200 的 IP 地址?
- 没有CU的情况下,如何将STARTER中的SINAMICS 项目下载到 CF卡
- 如何装载项目数据到存储卡上?以便在没有 TIA Portal 的情况下,使用存储卡向 S7-1200 /S7-1500CPU 传输程序
- 为什么在能够在线访问 S7-1500 CPU 的情况下却不能下载项目?
- 在没有 Internet Explorer 的情况下,如何使用 WinCC/WebNavigator 和 WinCC/DataMonitor?
- PCS7中在不使用Faceplate的情况下如何实现直接操作的功能
- 系统分区空间不足的情况下如何安装 TIA Portal 和 TIA Portal 更新包?
{{item.nickName}}